1. Use cold/hot aisle configuration, whenever possible, for maximising the cooling from the systems. When not using the configuration, blow the exhaust air right from a row of servers to the intake vents of next server row.
2. The cold aisles must be of 2 tiles wide always. Only place the perforated tiles in the aisles.
3. Install the brush seal cable grommet for keeping static pressure maximised under raised floor & get optimal delivery of the cold air into the cold aisles.
4. While installing as well as removing the communication cables or power whips, don’t remove more than the six raised tiles at the same time. Basically, removing them can cause a substantial drop on the static pressure under raised floor & cause the equipment to get overheat.
5. If you’ve CRAH or CRAC units, which are shut down or not actually used for maintenance, make sure to place Plexiglas cover over the unit’s top, for preventing the loss of any static pressure from back-flow under pressurized raised floor.
6. Blank off the positions of the unused server rack. Unblocked open racks may cause the bypass air from hot aisles to mix with the cold aisles tempering intake air to the servers.
7. Avoid creating the air dam build-up of the cables under raised floor that is going to interfere with the airflow. Run the communication and power cables in hot aisles. Don’t ever leave the fibre optic wire spools under raised floor; buy them to proper length. Build ups of cable generally block the movement of the air and create fire hazard.
8. Have a good maintenance program for ensuring that the CRAH/CRAC filters are changed on a daily basis. The dirty air filters may reduce output capacity of A/C units & contaminate under floor air plenum.
9. Check CFM output on every CRAH/CRAC unit to ensure they’re at the factory specifications. When its below the specs, you should know that you’re not getting maximum cooling experience which the unit is supposed to deliver. It’s even essential to know you’re not exceeding factory specs because this may cause draw off of amp to fan motors.
10. Don’t ever place the perforated tiles close to one another (closer than six feet) from the AC units. Air velocity that comes from unit may be so high that it can cause the air to be very much sucked into perforated tile. This is ineffective not only for cooling the servers but may even temper cold air under pressurised raised floor.
You must be logged in to post a comment.